Everything about steam traps in simple language: why steam condenses and why the water, air and carbon dioxide must be removed, the three ways a trap tells steam from water, the main types (float and thermostatic, inverted bucket, thermodynamic disc, bimetallic, balanced pressure), how to select and size one, stall, drip legs and warm-up loads, installation rules, flash steam and condensate return, air in steam, how to test a trap, what a leak costs, and the rules of thumb. Ten interactive animations.
SM
Sumit Mathur
24 min read
Steam is one of the best ways to carry heat around a plant. It is cheap, safe, easy to control, and it gives up a very large amount of heat at a steady temperature. But there is one thing it needs in return: every time steam gives up heat, it turns back into water, and that water must be removed. The device that does this is the steam trap.
A steam trap looks like a small, boring valve. Yet in a typical plant there are hundreds or thousands of them, and they decide how much heat the equipment really gets, how much steam is wasted, and whether the pipes bang with water hammer. This article explains how steam traps work, how to choose, size and install them, and how to tell if one has failed. Press the animations and move the sliders as you read.
1. Why steam turns into water
Steam heats by . When steam touches a cooler surface, it gives up its and becomes water at the same temperature. This is why steam is so good at heating: the heat released when 1 kg of steam condenses at 7 barg (about 2 050 kJ/kg) is about five times the heat needed to warm 1 kg of water from 0 °C to 100 °C.
The higher the pressure, the hotter the steam and the less latent heat each kilogram carries. Most process heating uses the latent heat. So the amount of condensate formed is simply
m˙condensate=hfg
where Q is the heat given to the process and h_fg is the latent heat. A heater taking 500 kW from 7 barg steam produces 500 ÷ 2 050 = 0.24 kg/s, about 880 kg of water every hour. All of it has to leave.
Three things collect in a steam heater and must be drained:
Condensate, the water formed from the steam.
Air, which came in with the feed water and when the plant was shut down and refilled.
Carbon dioxide, which comes from the boiler feed water. It dissolves in the condensate and forms carbonic acid, which corrodes the pipes.
2. What a steam trap does
A steam trap has three jobs:
Remove condensate as soon as it forms.
Vent air and carbon dioxide.
Hold back steam, so it stays in the heater and is not wasted.
It must do this automatically, at any load, for years, with nobody watching. That is a lot for a small valve, and it is why so many types exist.
Here is what happens to a heater when the trap is working, and when it is not.
Why a steam trap is needed
Heat output
100 %
Steam wasted (3 mm leak)
none
Condensate in the heater
10 % full
Trap
working
Condensate leaves as fast as it forms, and the steam stays in the heater. The whole coil is in steam.
When steam gives up its heat it turns back into water (condensate). That water, and any air, must leave the heater without taking steam with it. A steam trap is the automatic valve that does this. Pick a condition to see what happens to the heater if the trap does its job, passes steam, or does not pass condensate or air.
Things to try:
Failed open: the heater seems fine, which is the problem. Nobody notices a loss that is silent and constant. A 3 mm hole at 7 barg wastes about 21 kg of steam every hour.
Failed closed: the water backs up and floods the coil. Heat output falls. The cold water can also hit hot steam, which causes water hammer, and it corrodes the metal.
Air-bound: the heater has steam at full pressure but the output is low, because air has formed a blanket on the surface. (Section 9.)
3. How a trap tells steam from water
All traps must pass water and hold back steam, so they all need to tell them apart. There are three ways.
Family
How it tells steam from water
Types
Mechanical
By density. Water is dense and heavy. Steam is light. A float or bucket rises and falls
Float and thermostatic, inverted bucket
Thermostatic
By temperature. Condensate is a little cooler than steam. An element bends or swells as the temperature rises
By velocity. Fast flash steam under a disc lowers the pressure and snaps it shut
Thermodynamic disc
Use the explorer below. Pick a trap, then change what is arriving at its inlet: air at start-up, hot condensate, steam, or cooled condensate.
How each trap tells steam from condensate
Float and thermostatic (Mechanical)
How it works. A float rides on the condensate. When water arrives, the float rises and opens the valve. When steam arrives, the float drops and the valve shuts. A separate thermostatic element at the top lets air out.
Tells steam from water by: Density: float floats on water, sinks in steam.
Discharge. Continuous, modulating discharge. It matches the flow. Air venting: Very good (own air vent).
Good for. Large and changing loads, heat exchangers, unit heaters, coils and any place where the load swings.
Watch for. The float can be damaged by water hammer. The body can freeze if the trap is left full. Not for superheated steam.
All steam traps must pass condensate and air and hold back steam. They tell them apart in three ways: by density (mechanical traps), by temperature (thermostatic traps) or by speed (thermodynamic traps). Pick a trap and change what arrives at its inlet. Notice that thermostatic traps hold hot condensate back until it cools a little, while mechanical traps drain it as soon as it forms.
Notice the following:
Mechanical traps (float and bucket) drain hot condensate at once. The heater stays free of water. This suits a process that needs the surface fully in use.
Thermostatic traps hold hot condensate back until it cools by a few degrees (balanced pressure) or 10 to 30 °C (bimetallic). That backs up water in the heater, but it also uses the sensible heat of the condensate. It is fine for tracing and drips, but not for a fast controlled heater.
Thermodynamic traps open and close with a regular click. They are tough but need a minimum pressure to work.
Air at start-up is passed freely by the thermostatic types (cold air makes the element open). A float trap does it with a separate thermostatic vent.
The main types at a glance
Float and thermostatic
Inverted bucket
Thermodynamic disc
Bimetallic
Balanced pressure
Detects by
Density
Density
Velocity
Temperature
Temperature
Discharge
Continuous, matches the load
Intermittent
Intermittent (clicks)
Intermittent or continuous
Intermittent
Air venting
Very good
Fair
Poor when cold
Excellent
Excellent
Water hammer
Poor (float can be damaged)
Very good
Very good
Very good
4. Choosing a trap
There is no best trap. There is a best trap for the job. Tick the conditions of your application.
Which trap suits my job?
Tick one or more conditions below to see a shortlist.
Tick the conditions of your application. Each trap earns points for what it does well and loses points for what it does badly. The list is a starting shortlist. The final choice also depends on pressure, load, space, cost and the maker's advice.
A quick guide that follows industry practice:
Application
Usual choice
Why
Heat exchanger, coil, unit heater, process heater
Float and thermostatic
Handles large, changing loads and vents air. Drains at once
Steam main drip leg
Thermodynamic disc, or inverted bucket
Tough, resists water hammer, simple
Steam tracing
Balanced pressure or bimetallic
Small load, benefits from a little subcooling, frost resistant
Superheated steam drips
Thermodynamic disc (or a special thermostatic)
Other types lose their seal or the element fails
Very high pressure
Thermodynamic or bimetallic
Wide pressure range
5. Sizing a trap
The condensate load
For a heater that warms a product, the heat duty is
Q=m˙cpΔT
and the condensate load is Q divided by the latent heat of the steam, as in section 1.
Worked example. A heater warms 10 t/h of water by 40 °C with 7 barg steam.
Q = 10 000 × 4.18 × 40 ÷ 3 600 = 464 kW
Condensate = 464 × 3 600 ÷ 2 046 = 817 kg/h
With a safety factor of 3 (temperature-controlled heater), the design load is about 2 450 kg/h.
The pressure difference across the trap is 7 − 0.5 (back pressure) = 6.5 bar.
Pick a trap that can pass 2 450 kg/h at 6.5 bar. (In the animation this is the smallest generic size, “Size D”.)
The safety factor
A trap is never sized for the exact load. The factor covers:
the load at start-up, which is much higher than at run,
a fluctuating load,
a lower differential pressure than the design, when a control valve lowers the steam pressure.
Typical factors are 2 for a steady load and 3 for a temperature-controlled heater. The trap makers publish their own guidance. Use theirs.
The differential pressure
A trap passes condensate according to the pressure difference across it. If the heater is at 7 barg, and the condensate line is at 0.5 barg, the trap sees 6.5 bar. Lift (a vertical rise after the trap) takes pressure away: about 0.1 bar per metre. If the return line is at a higher pressure than the heater, the trap cannot drain it.
Sizing a trap: condensate load and differential pressure
Heat duty
464 kW
Condensate load
817 kg/h
Design load (× 3)
2451 kg/h
Differential pressure
6.50 bar
Smallest trap that passes it
Size D
Latent heat used
2046 kJ/kg
Use the lowest differential pressure the trap will see, not the highest. A trap sized at the supply pressure may be too small when a control valve lowers the steam pressure in the heater.
The condensate load follows from the heat the process needs: heat duty divided by the latent heat of the steam. The trap must pass more than that, so a safety factor is applied (typically 2 to 3). What a trap can pass depends on the pressure difference across it, which is the steam pressure minus the back pressure and any lift. Each grey line is one generic trap size. The green line is the smallest one that passes the design load. The sizes are illustrative: always use the manufacturer's capacity chart.
Things to try:
Raise the back pressure and watch the available differential pressure fall. At zero or below, nothing drains.
Add lift (say 10 m). That costs 1 bar.
Switch to the constant load setting. The design load and the trap size fall.
Look at the chart: capacity rises with the square root of the pressure difference. A big trap at a small pressure difference may pass less than a smaller one at a large difference.
6. Stall
Here is a problem that surprises many people. A heater with a temperature controller closes its steam valve when the load falls. The steam pressure in the heater falls with it. At low load, a small temperature difference is enough, so the steam only needs to be a little hotter than the product, and that means a low pressure, possibly below the pressure in the return line.
When that happens the trap has no pressure to push with. The condensate stays in the heater and floods it. This is called stall. The flooded surface loses heat, the controller opens the steam valve, the pressure rises, and the water is dumped in a rush. The cycle repeats and the product temperature swings.
Stall: why a trap floods a heater at low load
Pressure in the heater
0.87 barg
Pressure needed to drain
1.50 barg
Pressure to push the water
-0.63 bar
Stalls below a load of
47 %
Stalled: the heater is filling with condensate. Fix: a pump-trap (steam- or air-powered pump with a trap), a lower back pressure, a vented or vacuum-breaker arrangement, or a heater with a drain to atmosphere when it is at low load.
When a temperature controller throttles the steam, the pressure inside the heater falls, because less steam is needed at a smaller temperature difference. The pressure can fall until it is equal to the back pressure, or lower, and then the trap has nothing to push the condensate with. The heater floods and the product gets cold, then the pressure rises again and the water is dumped in a surge. This is called stall. The heat-transfer model is simplified: a fixed area, with the steam temperature set by the load.
In the default case (7 barg steam heating a product at 90 °C, return line at 1.5 barg), the heater stalls below about 47 % load. If the heater runs below that load much of the time, as many do, it floods most of the day.
Solutions:
Use a pump-trap: a combined pump and trap, driven by steam or air, that can push condensate against back pressure.
Lower the back pressure, or remove the lift.
Use a vacuum breaker and a drain to a safe place, for heaters that stall at low load.
Control the heater on the condensate side, or use a steam-pressure-controlled arrangement that keeps the heater pressure up.
7. Installation
Draining a steam main
The main must be laid with a slope in the direction of flow (about 1 in 100, or 10 mm per metre), so the condensate runs to the drain points. At each drip leg, a pocket collects the condensate and a trap removes it.
Put a drip leg:
every 30 to 50 m on a long straight main,
at the end of the main,
at every low point,
ahead of control valves, shut-off valves, and anything that holds condensate back,
before a rise (a riser), and
at the inlet of each piece of equipment.
Drip pocket size. For a main up to DN100 the pocket has the same diameter as the main. For larger mains it is about half the main diameter (and not below DN100). The pocket should be at least 250 mm long (about 1.5 pipe diameters), so there is room for the water to collect below the take-off point.
Draining a steam main: drip legs and the warm-up load
Drip legs and traps
6
Pipe falls by
1.5 m over the run
Condensate to warm up the main
89 kg
Warm-up load per trap (30 min)
30 kg/h
Running load per trap
2.4 kg/h
Drip pocket
DN100, at least 250 mm long
A trap must be big enough for the warm-up load, but it spends most of its life on the much smaller running load. This is why a trap that is much too large on a drip is not a problem, but a heater trap sized for the wrong load can be. Warm-up is also when water hammer happens, so open the main steam valve slowly and use the by-pass.
Condensate forms all along a steam main, and it forms fastest when the cold main is first warmed up. The main is laid with a slope in the direction of flow (about 1 in 100), and condensate is caught in a drip leg and removed by a trap. Drip legs go at least every 30 to 50 m, at the end of the main, at low points and ahead of anything that stops condensate: control valves, risers and shut-off valves. Change the length, pipe size and insulation to see the load on each trap.
Notice that the warm-up load is much bigger than the running load. A cold main must be heated up, and the steel takes heat from the steam. The trap on a drip must handle the warm-up load, and it is during warm-up that water hammer happens. Open the main steam valve slowly, and use the by-pass.
The layout of one trap
A good trap station, in the order along the line:
Isolation valve (so the trap can be taken out),
Strainer (to protect the trap from scale and dirt),
A test point or sight glass,
The trap,
A check valve (to stop backflow when the return line is higher in pressure),
Isolation valve,
The line to the return.
The most important rules:
One trap for each heater, or each drip point. Do not “group-trap” two heaters on one trap: the one with the lower pressure will fill with water.
Fit the trap below the outlet of the equipment, with a short, falling line to it.
Do not lift the condensate after the trap unless the steam pressure is enough (and then add a check valve). Lifting costs about 0.1 bar per metre.
Connect each trap outlet into the top of the return line, so that the condensate is not pushed back into the next trap.
Do not join traps of different pressures into one line without check valves.
Size the return line for flash steam (section 8), not just for water.
Put air vents at the high point of heaters and coils.
8. Flash steam and the condensate return
Condensate leaving a heater at 7 barg is at 170 °C. When it goes through the trap into a line at atmospheric pressure, where water boils at 100 °C, it holds more heat than it can keep as a liquid. The excess boils off immediately as flash steam. The share is
flash fraction=hfg2h
where h_f1 is the heat of the liquid at the high pressure, h_f2 and h_fg2 are the heat of the liquid and latent heat at the low pressure.
Flash steam: what happens when hot condensate loses pressure
Flashes to steam
13.4 %
Flash steam
134 kg/h
Share of the volume that is steam
99.6 %
Heat you could recover
84 kW
At 7 barg, going to atmospheric pressure, about 13 % of the condensate by mass flashes. By volume the line is over 99 % steam. Size return lines for this two-phase flow, never for the water alone. A flash vessel separates the steam, which can feed a lower-pressure steam user, and sends the water on.
Condensate at the steam pressure is at the steam temperature. When it passes through the trap into a line at a lower pressure, it is suddenly hotter than the new boiling point, and part of it boils off at once as flash steam. The share that flashes is the extra heat in the water divided by the latent heat at the new pressure. Because steam takes up hundreds of times more volume than water, the return line is mostly steam by volume, even if it is only a few per cent by mass. That flash steam can be recovered and used.
From 7 barg to atmospheric about 13 % of the condensate by mass flashes. That sounds small, but steam takes up about 1 700 times more volume than water at atmospheric pressure. So the pipe is 99.6 % steam by volume. This has three consequences:
Size the return pipe for the two-phase flow. An undersized line has high velocity, noise, erosion and water hammer. A common guide is to keep the speed in a flashing return line below about 15 m/s.
Flash steam is free heat. In a flash vessel, the steam is separated from the water and can feed a lower-pressure heater, a de-aerator or a space-heating system.
The condensate itself is valuable: it is hot, pure water. Returning it to the boiler saves fuel, water and treatment chemicals.
Also, steam seen blowing out of a condensate vent is often flash steam, not a leaking trap. This is one reason that trap testing needs care.
9. Air and carbon dioxide
Air does not condense. It collects next to the heating surface as a blanket, and the steam must reach the metal through it. Two things happen:
The steam partial pressure falls, so the temperature of the mixture is lower than the steam temperature on the pressure gauge. With 5 % air in 7 barg steam, the temperature falls about 2 °C.
The air layer blocks heat transfer. Even a small percentage can cut the heat output a lot. (The curve in the animation shows the trend. It is not a design equation.)
Air in steam: a cold blanket on the heating surface
Steam temperature without air
170.5 °C
With the air
169.6 °C
Temperature lost
0.9 °C
Heat transfer (illustrative)
20 %
Also, carbon dioxide dissolves in the condensate and forms carbonic acid, which corrodes the condensate lines. Good air venting at start-up, and a trap that passes air (thermostatic or float-and-thermostatic), cures both problems. Heat exchangers should have an air vent at their high point as well.
Air and carbon dioxide come in with the feed water and when plant is started. They do not condense, so they pile up against the heating surface and the steam has to reach the wall through them. Two things happen: the steam partial pressure falls, so the steam temperature at the wall is lower for the same total pressure, and the air layer is a barrier to heat transfer. The steam-temperature drop here is physics (Dalton's law). The heat-transfer curve is an illustration of the trend. This is why every trap system must vent air.
The remedy is a trap that vents air easily (thermostatic or float-and-thermostatic), plus an air vent at the high point of the equipment, plus careful start-up. Carbon dioxide dissolves in the condensate and forms carbonic acid. This attacks carbon steel return lines. A good de-aerator at the boiler, and proper venting, reduce it.
10. Testing and maintenance
Traps fail quietly. A trap that has failed open loses steam but no one sees it. A trap that has failed closed shows up as a cold heater, or a banging pipe. Studies of plants that never check their traps often find that a large share of them have failed. Many plants that start a regular survey find the percentage falls to a few per cent within a year or two.
There are four ways to test a trap:
Method
What it shows
Weakness
Look at the discharge (test valve or sight glass)
Steady steam plume means blowing
Flash steam looks like a leak. Needs safe access
Listen (stethoscope or ultrasonic tester)
Each trap type has its own sound: a click, a gentle flow, or a steady roar
Needs training. Ultrasonic testers are reliable
Temperature before and after (infrared thermometer)
A cold trap (and cold heater) shows failed closed
A hot outlet can be flash steam. Not proof of a leak
Condensate flow or trap monitor
Fixed, continuous monitoring
Cost. Used for critical traps
Use two methods. Never decide on temperature alone.
Is this trap working? Testing by sound, temperature and sight
Verdict
Working: cycling type
Temperature drop across it
60 °C
A clean click as it opens and shuts, with small puffs of flash steam. This is how disc, bucket and many thermostatic traps behave.
Traps are tested in three ways: by looking at the discharge, listening to it (a stethoscope or ultrasonic tester), and measuring the temperature before and after the trap. No single sign is enough. Set what you observe and see the verdict. The temperature after a trap depends on the return pressure and the flash steam, so a hot line alone does not prove a leak.
A good management programme
List and tag every trap (type, size, location, duty).
Test them on a schedule: critical, high-pressure traps every few months, others yearly.
Repair or replace failed traps promptly, and record the result.
Review the failure rate, and learn why they fail (wrong type, dirt, water hammer, wrong size).
What a leak costs
The loss through a leaking trap follows the size of the hole and the steam pressure. The steam loses through a hole is easy to calculate, and the result is surprising: a small leak running all year costs more than the trap.
What a leaking trap costs
Steam lost per year
168 t
Cost of this one trap
5,052 / yr
CO₂ (gas-fired boiler)
29 t / yr
60 failed traps cost
303,108 / yr
This does not count the cost of the extra boiler fuel and water treatment, the extra load on the condensate return, or the lost production when a trap fails closed. A trap survey usually pays for itself within a year. About 0.17 t of CO₂ per tonne of steam is a typical figure for a natural-gas boiler.
A trap that has failed open lets steam pass into the condensate line. The flow through a small hole is easy to estimate: steam through a hole at high pressure is choked, so the loss grows with the hole area and the pressure. Even a 3 mm hole is worth thousands a year. The second part adds up a whole plant. Costs are in any currency per tonne of steam. The failure rate is only an example. Plants that never survey their traps often find that a large share have failed.
11. Rules of thumb
These are typical industry guides. Always check the maker's data and your own standard.
Topic
Rule of thumb
Job of a trap
Remove condensate, vent air and CO₂, hold back steam
Condensate load
Q ÷ latent heat. At 7 barg about 1.8 kg/h of condensate for each kW of heat (500 kW gives about 880 kg/h)
Safety factor
2 for a steady load, 3 for a temperature-controlled heater. Use the maker's value
Differential pressure
Steam pressure − back pressure − 0.1 bar per metre of lift
Drip legs on a main
Every 30 to 50 m, at the end, at low points, before valves and risers
Slope of a steam main
About 1 in 100 in the direction of flow (10 mm per metre)
Drip pocket
Same size as the main up to DN100. About half for larger mains, not under DN100. At least 250 mm long
Trap for a heater
Float and thermostatic. Never share a trap between heaters
Trap for a drip
Thermodynamic disc or inverted bucket
12. Common mistakes
Choosing the trap for the supply pressure, and forgetting that the heater pressure can fall far lower at part load. This causes stall.
No strainer. Scale jams a trap in a few days.
One trap for several heaters. The one at the lower pressure floods.
Oversizing “to be safe”. A trap that is far too big wears out its seat and cycles badly. Use the maker's data and a sensible factor.
Lifting condensate after the trap with no check valve, or with too little pressure.
A return line sized for water only, so the flash steam makes it noisy and gives back pressure that stalls the traps.
Forgetting air venting at the high point.
No drip leg ahead of a control valve, so water slugs hit the valve and the process.
Testing by temperature alone.
Never testing. A trap programme is cheaper than the steam it saves.
Summary
Steam heats by condensing, and the condensate, air and CO₂ must be removed. A steam trap does this automatically while holding steam back.
Mechanical traps tell steam from water by density, thermostatic traps by temperature and thermodynamic traps by velocity. Each type suits different jobs.
Heaters generally use float and thermostatic traps. Drips use disc or bucket traps. Tracing uses balanced-pressure or bimetallic traps.
Size a trap from the condensate load (heat duty ÷ latent heat), a safety factor of 2 to 3, and the real differential pressure.
A controlled heater can stall at part load, when the steam pressure falls below the back pressure. A pump-trap or lower back pressure fixes it.
Slope the steam main, put drip legs every 30 to 50 m and ahead of every obstruction, and fit a strainer, a test point and a check valve at each trap.
Flash steam is about 13 % of the condensate by mass from 7 barg to atmospheric. It fills the return line, so size it for two-phase flow, and recover it if you can.
Air in steam lowers the temperature and blocks the surface. Vent it.
Test traps with two methods, regularly. A small leak that runs all year costs far more than the trap.
Q
Poor
Superheated steam
No
No (loses its water seal)
Yes
Some
No
Frost
Can freeze
Can freeze
Resists
Resists
Fair
Backs up condensate
No
No
No
Yes (subcools)
A little
Typical use
Heaters, coils, large changing loads
Steam main drips
Drips, tracing, high pressure
Tracing, drips
Tracing, small equipment
Condensate that must be lifted or has back pressure
Pump-trap, see section 6
A trap alone cannot drive it
f1
−
hf2
Trap for tracing
Balanced pressure or bimetallic
Check valve
Fit one after the trap if the return line can be at a higher pressure, or is lifted
Strainer
Always, ahead of the trap
Flash steam
About 13 % by mass from 7 barg to atmospheric. 99 % of the volume is steam
Return line
Size for flash steam. Keep the velocity below about 15 m/s
Leak
A 3 mm hole at 7 barg loses about 21 kg/h, around 170 tonnes a year
Air
5 % air by volume lowers the steam temperature by about 2 °C at 7 barg. Always vent air
Testing
Use two methods. Critical traps every few months, others at least yearly
Water hammer
Open steam slowly, use the by-pass, slope the main, drain every low point