Shell & Tube Heat Exchangers, Part 1: U, LMTD, Approach and the Correction Factor
Where the overall heat transfer coefficient really comes from, why counter-current wins, what a temperature cross is, how Ft works, and which fluid goes on the shell side. Four animations you can drag.
SM
Sumit Mathur
18 min read
A shell and tube exchanger looks like a steel barrel full of tubes. Under the hood it is a very small number of ideas, repeated. If you understand five of them (the overall coefficient, the flow arrangement, the mean temperature difference, the approach, and the correction factor) you can read almost any exchanger datasheet and tell whether it is sensible.
This is Part 1 of a 7-part series that walks the whole design process of a refinery-style shell and tube exchanger, from first principles to a hand-sized design and a reboiler. Every part has animations you can pause and push. If you want to size something right now, the Heat Exchanger tool in this app does the full rating.
1. The only equation that matters
Heat moves from the hot stream to the cold stream through a wall. The rate is proportional to the area and to the temperature difference that drives it:
Q is the duty, A the surface area, ΔTm the effective mean temperature difference, and U the overall heat transfer coefficient, the constant of proportionality that hides everything messy about fluids, metal and dirt.
Two ways to move a design forward fall straight out of this: get more driving force, or get more area. Every other decision in this series is a way of buying one of the two cheaply.
2. Where U comes from: resistances in series
In a clean exchanger, heat has to cross three things in sequence: the fluid film on the inside of the tube, the tube wall, and the fluid film on the outside. As the unit ages, a deposit builds on each surface, and those two fouling layers are added to the list. Five resistances, one after the other, like resistors in a circuit:
U1=h
(By convention every term is referred to the outside surface of the tube, which is why the inside film is written hio.)
Drag the sliders below. Each layer's width is proportional to its resistance, and the red line shows how the temperature drops across the stack.
Animation – Five resistances in series: what really sets U
U clean
472 W/m²K
U fouled
397 W/m²K
Extra area for fouling
+19 %
Controlling
Shell-side film
Heat has to cross every layer in turn, and each layer eats a share of the temperature drop in proportion to its resistance. The fattest layer is the controlling resistance: improving anything else barely moves U.
Three habits to take away from playing with it:
The biggest resistance rules. If one film is five times worse than the other, doubling the good film improves U by a few percent. Find the controlling resistance before you spend effort on anything.
Tube wall is usually negligible. For thin carbon-steel tubes it rarely reaches 1 % of the total.
Fouling is a tax you pay in area. The "extra area for fouling" readout is the surface you must buy up front so the exchanger still works when dirty.
Clean, actual and required U
Engineers use three versions of U, and mixing them up is a classic source of confusion:
Name
Meaning
Uclean
Films and wall only: a brand-new exchanger
Uactual
Clean value with the fouling resistances added: what the unit does when dirty
The overdesign is the margin by which what you built beats what you need:
%overdesign=100(UrequiredU
A common practice is 10–20 % overdesign on small exchangers and about 5 % on large ones, where the cost of excess area is high. One subtlety: if the two outlet temperatures in a single shell are nearly equal, the LMTD is so sensitive that a big overdesign changes the exchanger's thermal performance very little. Don't trust the percentage blindly.
3. Flow arrangement: why counter-current wins
Fluids can run co-current (same direction), counter-current (opposite) or cross-flow (at right angles, as in air coolers and some shell types). Switch between the first two below and watch the gap between the two temperature lines:
Animation – Counter-current vs co-current: where the driving force goes
ΔT hot end
50.0 °C
ΔT cold end
50.0 °C
LMTD
50.0 °C
Approach
50.0 °C
Hot fluid enters at 150 °C and cold at 30 °C. In counter-current flow the two streams keep a healthy gap along the whole length. In co-current flow the gap collapses at the outlet and the cold stream can never leave hotter than the hot stream.
In co-current flow the cold stream can never leave hotter than the hot stream, so you throw away driving force. Counter-current keeps a useful gap the whole way, which means a higher mean temperature difference for the same terminal temperatures and therefore less area. Co-current is only chosen deliberately, for example when you want to guarantee a minimum wall temperature while cooling a high pour-point liquid.
The log mean temperature difference
When the temperature difference varies along the exchanger, the average that belongs in Q=UAΔTm is the logarithmic mean:
LMTD=ln(ΔT1/ΔT
where ΔT1 and ΔT2 are the temperature differences at the two ends. The derivation assumes:
U is constant along the exchanger.
Flow rates and specific heats are constant.
No phase change (unless it is a pure component with no sensible-heat effect).
Heat losses are negligible.
Real services violate some of these. When a multi-component stream condenses or boils, split the exchanger into zones, compute an LMTD per zone, and form a duty-weighted average (often called the EMTD, the equivalent mean temperature difference). The EMTD is not the same thing as a "corrected LMTD", which only corrects for flow pattern and does not break the unit into zones.
4. The approach temperature
The approach is the smallest temperature gap anywhere between the two curves. For a counter-current exchanger it is the smaller of (hot in − cold out) and (hot out − cold in); for co-current it is hot out − cold out. It is not always at an end, so check the heating and cooling curves when there is a phase change.
Quick example. Hot fluid 95 → 40 °C, cold 25 → 35 °C. Counter-current approach = min(95 − 35, 40 − 25) = 15 °C. Co-current approach = 40 − 35 = 5 °C. Same terminal temperatures, three times the margin.
Typical minimum approaches for a conservative single-pass-shell design:
Service
Approach, °C
Cryogenic coil exchanger
3–5
Gas chill-down
~6
Cooling-water cooler
6–8
Gas compression intercooling
10–15
Condenser on cooling water
10–15
Hydrocarbon product vs cooling water
15–20
Condenser on air
15–20
Reboiler on steam
~17
Reboiler on hot oil
~22
Hydrocarbon vs air, hydrocarbon vs hydrocarbon
20–25
A tight approach means a small LMTD, which means a lot of area. Approach is where economics enters thermal design.
5. Temperature cross and the correction factor Ft
Most shell and tube exchangers are not purely counter-current. With two or more tube passes, some of the tube length runs in the same direction as the shell fluid, and baffles add cross-flow. To account for it we multiply the counter-current LMTD by a factor Ft<1:
ΔTm=Ft⋅LMTD
Ft depends on two dimensionless numbers built from the terminal temperatures:
S=Thi−
S is the thermal effectiveness (how much of the available temperature span the cold stream picks up) and R is the heat-capacity ratio. A temperature cross exists when the hot stream leaves colder than the cold stream, which a pure counter-current unit can do but a single multipass shell cannot do efficiently. Move the sliders and watch Ft plunge:
Animation – The LMTD correction factor Ft
R
1.00
S
0.04
Ft
1.000
Min. shells (est.)
1
S measures how much of the available temperature span the cold stream picks up; R compares the two stream duties. As S climbs, Ft falls off a cliff. Keep Ft above 0.8, or split the duty over several shells in series.
Rules every process engineer carries:
Keep Ft above about 0.8. Below that, the curve is so steep that a tiny error in a temperature swings the required area wildly, and the design is fragile.
If it falls below 0.8, add a shell in series (you will see how in Part 5) or switch to a shell type that gives true counter-current flow.
Economics decides how high Ft should be. On large duties a drop from 0.95 to 0.90 is a lot of extra steel, so the target is higher; on a small duty you can live with 0.85.
Ft assumes equal area in every pass, a constant U, constant temperature in each shell-side pass, and no leakage between passes. Shell types with split flow (J, X) have different Ft charts from E shells for the same temperatures.
6. Which fluid goes on the tube side?
Fluid allocation is the first decision you make and the hardest to undo. These are the usual reasons, and the logic behind each:
Put it in the tubes if it is:
Treated cooling water. Corrosion and scaling then attack only one side, inhibitors work well, and the tubes are easy to clean.
Corrosive or very hot. Alloy is expensive. Putting the fluid in the tubes means only the tubes and heads need the good metal, not the whole shell. It also loses less heat to the environment.
The higher-pressure stream. Small-diameter tubes carry pressure far more cheaply than a big shell.
Fouling. Tubes can be cleaned straight through. The shell side has dead zones where dirt collects.
Low flow. Passes can be added to raise velocity.
Viscous in laminar flow. The small cross-section of the tube side can still make turbulence.
Put it in the shell if it is:
Changing phase. Condensate or vapour moves freely and you avoid awkward two-phase regimes in small tubes.
Viscous (above about 2 cP). The baffled shell side promotes turbulence at low Reynolds number.
The stream with the lowest film coefficient (a clean gas, for instance), since you can add fins or choose a pitch to improve the outside.
Short of pressure drop. J or X shells can give very low shell-side losses.
Part of a large temperature difference across a single bundle (above about 200 °F, multi-pass). Keeps stress off the tubesheet.
When two guidelines conflict, fouling and corrosion usually win over everything else.
7. What you need before you start
Gather these before opening a calculator. Missing any of them is the single biggest cause of an exchanger that does not work:
Streams: flow rate, physical properties, in and out temperatures and pressures, allowable pressure drop, phase, whether it boils or condenses, fouling tendency, corrosion potential.
The output of the thermal design is a datasheet and a tube-layout drawing produced from rating software such as HTRI, handed to the manufacturer.
What's next
U and Ft tell you how big the exchanger must be. Part 2 opens the shell and chooses the tubes: pitch, diameter, thickness, length and number of passes.
io
1
+
Rfidido+
Rw+
Rfo+
ho1
Urequired
Q/(A⋅EMTD): what the process needs the unit to deliver