Shell & Tube Heat Exchangers, Part 4: TEMA Types, Materials and Mechanical Design
Decode AES, BEM, BEU and AKT with an interactive TEMA builder, then learn fixed vs U-tube vs floating head, material selection, design pressure and temperature, the 10/13 rule, allowable pressure drop and the piping details that get forgotten.
SM
Sumit Mathur
20 min read
Open any exchanger datasheet and you'll see three letters: AES, BEM, BEU. Those letters, defined by the Tubular Exchanger Manufacturers Association (TEMA), tell an experienced engineer the whole mechanical layout of the unit at a glance. This article teaches you to read them, then covers the mechanical design basis: materials, pressures, temperatures and pipework.
This is Part 4 of 7. Part 3 covered baffles and shell-side flow.
TEMA defines three construction classes for unfired exchangers:
Class
For
Notes
R
Severe petroleum and related duty
Used for essentially all refinery exchangers
B
Chemical process service
More stringent than C, less than R
C
Moderate commercial and general duty
Can save around 5 % vs R when the design allows chemical cleaning and fouling is under about 0.00035 m²·K/W on both sides
2. Three construction families
Before the letters, the single biggest choice is how the tubes are allowed to expand relative to the shell.
Fixed tubesheet
Both tubesheets are welded to the shell. The cheapest design, with the fewest leak paths, but the outside of the tubes cannot be cleaned mechanically.
Choose it when the shell side is non-fouling or chemically cleanable, and the shell-to-tube temperature difference stays under roughly 50–60 °C (up to about 80–90 °C with a shell-side expansion bellows).
Check the temperature difference across all operating cases, not just normal: shell-side start-up with no tube fluid, tube-side start-up with no shell fluid, pressure failure of either side, turn-down, hydrotest and steam-out.
A packed-gland expansion joint is acceptable only for water, steam or air shell sides. Otherwise use an internal bellows, designed for a minimum fatigue life of about 7000 cycles.
Used in refineries for high-temperature process-side steam generators (above ~540 °C) and for all vertical thermosiphon reboilers.
U-tube
One tubesheet, tubes bent into hairpins. They expand freely, the bundle slides out, and the cost is low. The inside of the bends is hard to reach, so it is for clean tube-side service: select it when the shell-to-tube ΔT exceeds ~50–60 °C and tube-side fouling is low (below about 0.00045 h·m²·°C/kcal). Leave at least 150 mm between the parallel legs if you intend any mechanical cleaning.
Floating head
A floating tubesheet moves with the bundle, which can be pulled out for shell-side cleaning. Choose it when ΔT is large and the tube side fouls (above about 0.00045). The price is more joints, more weight and more money. Because of the extra leakage stream (E), fixed designs are thermally slightly more efficient than floating-head ones.
3. Build your own TEMA code
The first letter is the front head, the second the shell, the third the rear head. Choose one from each group, or press a preset to see a common refinery pairing:
Interactive – Build a TEMA designation: front head · shell · rear head
1 · Front head
2 · Shell
3 · Rear head
Front A
Channel + removable cover
Open the cover and every tube end is in view. First choice for tube-side fouling or cooling water. One extra gasketed joint, so less suited to very high pressure.
Shell E
One-pass shell
The workhorse. Single inlet, single outlet, any duty without phase change.
Rear S
Floating head, split ring
Floating head held by a split backing ring inside a larger shell cover. Cheap, but slow to open and not for corrosive duty.
Construction: Floating head: the bundle expands freely and comes out for shell-side cleaning, at the price of more joints and money. AES in practice: Refinery workhorse: dirty shell side, big ΔT, frequent tube cleaning.
Every TEMA exchanger is named with three letters. Pick one from each group to see what the combination looks like and what it is good for. The presets are the common refinery pairings.
Front-head guidance
A (channel + removable cover) when the tube side needs frequent cleaning (fouling above ~0.00035 m²·°C/W). You can see every tube end by removing the cover. It adds one joint, so it is less suited to high pressure.
B (bonnet) when the tube side is clean or chemically cleaned, or in leak-sensitive duty such as LPG. Cheaper than A.
C for higher pressure, N for very clean services and horizontal thermosiphon reboilers, D for the highest pressures.
Selection between A and B varies by company; some default to B and use A only for cooling-water exchangers under ~10 kg/cm²g, others do the opposite.
For special high-pressure closures, the product of channel closure diameter (in) and tube-side design pressure (psig) decides the route: below 60,000, a normal TEMA design works; between 60,000 and 90,000 it is an economic choice; above 90,000 only the special closure applies.
Shell-type guidance
E: the one-pass shell for most single-phase duty.
F: two-pass with a longitudinal baffle, to dodge a temperature cross in a single shell. Downsides: leakage across the baffle, difficult bundle removal. Limit ΔT to roughly 139 °C and keep the shell-side pressure moderate; many companies avoid F for mechanical reasons.
G / H: split and double-split flow, for horizontal thermosiphon reboilers (G for tubes under ~3 m).
J: divided flow for gas duty and low ΔP.
X: cross-flow with almost no pressure drop across the bundle, for vacuum condensers.
K: kettle, for boiling on the shell side.
For pressure drop, the order is E (highest) > J > X (lowest).
Rear-head guidance
L, M, N: fixed tubesheet. M is the usual cheap choice (BEM); L is chosen with an A front head and an odd number of passes.
P, W: low pressure and temperature only (W below about 190 °C), not common in refineries.
S: floating head with a split backing ring and an oversized shell cover. Low capital cost, high maintenance cost and time. Not for corrosive service or very fouling shell sides.
T: pull-through floating head. The entire bundle, floating head included, comes out of the stationary end, so maintenance is quick. It's the most expensive, because the shell must be enlarged. Preferred over S for heavy shell-side fouling (above about 0.00088 m²·°C/W), very large shells, and congested sites where reaching a split ring is impossible. A kettle that needs a floating head takes a T.
U: U-tube bundle.
Worked examples from refinery practice
Duty
Typical TEMA
Low-pressure feed preheater, steam in tubes
BEU
Feed preheater on a dirty bottoms stream
AES / AET
Reboiler on a column, steam in tubes
BHU (G, J, X, or AKU also possible)
HP steam generator, fouling tube side
AKT
Reactor effluent / cold feed, very high pressure
DEU / DFU
Vapour feed/effluent exchanger with very low shell ΔP
BXU
Vertical thermosiphon reboiler
NEN
4. Materials of construction
Material choice rests on temperature and corrosion. The static-equipment specialist signs off the final specification, but you must set the process basis.
Temperature
Suggested metallurgy
Below −45 °C
9 % nickel steel, austenitic stainless, titanium or aluminium alloys
−29 to −45 °C
Silicon- or aluminium-killed carbon steel
Up to ~540 °C
Carbon steel (carbon–½ Mo for extra strength)
~540–650 °C
1–1¼ Cr–½ Mo, with silicon to prevent graphitisation
~650–815 °C
Austenitic stainless; steam reformers use high-nickel alloys
For corrosion: hydrogen-free sulphide attack is handled with carbon steel up to about 260 °C, 5 Cr–½ Mo steel above; hot hydrogen service is selected from the Nelson curves (API 941); sea water calls for admiralty brass, 70/30 Cu-Ni or titanium.
5. Design pressure
Set the design pressure at the highest of:
The shut-off pressure of an upstream pump, if the exchanger can be blocked in against it.
The normal differential pressure of an upstream pump at relief-case suction pressure.
An identifiable upset.
The table below:
Maximum operating pressure (MOP)
Design pressure
< 1.72 barg (25 psig)
3.45 barg (50 psig)
1.72–17.2 barg
MOP + 1.72 bar
> 17.2 barg
MOP + 10 %
Equipment that can see vacuum is also designed for full vacuum. A minimum design pressure of about 5.1 kg/cm²g (75 psig) applies to either side, and 10.2 kg/cm²g (150 psig) on the cooling-water side of coolers.
If the cold side is liquid and can be blocked in full, fit a thermal relief valve set at its design pressure (the same trap shown in the PSV article's blocked-in line). If the hot side is a low-pressure liquid that could cool and pull a vacuum, design for about 1.03 kg/cm²g external pressure.
The 10/13 rule: protecting the low-pressure side
If a tube fails, the high-pressure fluid floods the low-pressure side. A shell is hydrostatically tested at 130 % of its design pressure, so
Pdesign,LP≥13
means the low-pressure side has been proven by test to withstand the HP side's design pressure. Then no relief device is needed for tube rupture. (The older rule was 2/3, from when hydrotests were 150 %.) Slide the LP design below the threshold and see what happens:
Animation – The 10/13 rule and tube rupture
LP / HP design
77 %
10/13 minimum
30.8 barg
LP proven to
40.0 barg
Verdict
No relief needed
If a tube splits, the high-pressure fluid floods the low-pressure side. Because the shell is hydro-tested at 1.3 × its design pressure, a low-pressure side designed at 10/13 (≈ 77 %) of the high-pressure side has already been proven at the high-side pressure, so no relief valve is needed for tube rupture.
If the low-pressure side is under 10/13, treat tube rupture as a credible relief scenario and size protection for it.
6. Design temperature and MDMT
Operating temperature
Design temperature
Ambient to 316 °C
Max operating + 13.9 °C (25 °F)
Above 316 °C
Max operating + 27.8 °C (50 °F)
−9 °C to ambient
Min operating − 13.9 °C
−23 to −10 °C
Min operating − 11.1 °C
−62 to −23 °C
Min operating − 5.6 °C
Below −62 °C
Min operating temperature
The minimum design metal temperature (MDMT) matters because steel turns brittle in the cold. Combine the lowest ambient temperature with any auto-refrigeration (a flashing liquid) to set it, and never pressurise a cold exchanger.
7. Allowable pressure drop
For pumped liquids, per shell:
Viscosity, cP
Shell side, kg/cm²
Tube side, kg/cm²
< 1
0.17
0.34
1–5
0.34
0.51
5–15
0.51
0.68
15–25
0.68
1.02
25–50
1.02
1.70
> 50
per exchanger specialist
per exchanger specialist
Cooling-water coolers: about 1.02 kg/cm² on the water side, plus 0.34 kg/cm² allowed for throttling in system design.
Fouling services: leave 30–40 % margin between allowable and calculated ΔP.
Condensers: roughly 0.1 kg/cm² per shell below 50 psig, 0.2 for 51–200 psig, 0.3 above 200 psig (vacuum columns may need less).
Thermosiphon reboilers: size so that only about half (up to 75 % on large installations) of the available hydrostatic head is used by the process-side pressure drop.
8. Piping and mechanical details people forget
Vents and drains: keep them to a minimum, but a total-condensing shell needs a 50 mm vent opposite the inlet, and a tube-side condenser needs a vent at the high point of the last pass. Floating-head shell covers need a vent and drain.
Block valves: use high-point vents and low-point drains (about 40 DN) on piping to exchangers or stacked banks without individual block valves, plus spectacle blinds or spacers.
Isolation: provide block and bypass valves if the unit has to be isolated while the plant runs, or if a leak would intolerably contaminate the other stream. Avoid isolation valves on reboilers; otherwise an extra PSV is required, and the valve's resistance disturbs the hydraulics.
Hydrogen service: 6″ and larger flanged joints above 200 °C that are hard to reach should have smothering-steam rings.
Cooling water: include back-flush facilities and a sample point on the outlet line to detect leaks. Heavy-hydrocarbon units need permanent flushing-oil connections.
Temperature control: use a simple bypass with two valves, or a three-way valve, which is needed when the exchanger's own ΔP is so low that a plain bypass would not divert enough.
Insulation: for hot shells, approximate thickness is 65 mm (60–150 °C), 75 mm (151–230 °C), 100 mm (231–300 °C), 125 mm (301–400 °C) and 165 mm (401–600 °C).
Summary
Pick the family first (fixed / U / floating) from ΔT and fouling.
Read TEMA as front · shell · rear.
Set design pressure to the worst credible case, and keep the LP side at ≥ 10/13 of the HP side.
Check materials against both temperature and corrosion.
Part 5 is about tuning a working design: series and parallel arrangements, trading h against ΔP, and avoiding tube vibration.